We goal to see good quality disfigurement within the manufacturing and provide the most effective support to domestic and overseas shoppers wholeheartedly for Compressor Capacitor, Capacitor Bank Contactor, Water Motor Capacitor, The principle of our company is to provide high-quality products, professional service, and honest communication. Welcome all friends to place trial order for creating a long-term business relationship.
Power Quality Cabinet – HYSPC three-phase load imbalance automatic adjustment device – LASTONE Detail:
Overview
Three-phase imbalances are common in low voltage distribution networks. Due to the existence of a large number of singlephase loads in urban and rural networks, the current imbalance between the three phases is particularly serious.
The current imbalance in the power grid will increase the loss of the line and transformer, reduce the output of the transformer, affect the operation safety of the transformer, and cause zero drift, resulting in three-phase voltage imbalance, and reduce the quality of power supply. In view of the above situation, our company have developed three-phase unbalanced automatic regulation device for the purpose of optimizing power quality and realizing energy conservation and emission reduction.
The device filters over 90% of the zero sequence current and controls the three-phase imbalance within 10% of the rated capacity.
Model and Meaning
| HY |
SPC |
- |
 |
- |
 |
/ |
 |
|
 |
|
 |
|
| │ |
│ |
|
│ |
|
│ |
|
│ |
|
│ |
|
│ |
|
| 1 |
2 |
|
3 |
|
4 |
|
5 |
|
6 |
|
7 |
|
| No. |
Name |
Meaning |
| 1 |
Enterprise code |
HY |
| 2 |
Product type |
three phase imbalanced regulation |
| 3 |
Capacity |
35kvar、70kvar、100kvar |
| 4 |
Voltage level |
400V |
| 5 |
Wiring Type |
4L: 3P4W 3L: 3P3W |
| 6 |
Mounting type |
outdoor |
| 7 |
Door opening mode |
No marked: the default is front door opening, wall mounted installation; Side door opening, plug-in three-phase four wire installation must be specified |
* Note: The parameters and dimensions of HYSPC module and HYSVG module on page 25 are the same
Technical Parameters
| Normal working and installation conditions |
|
| Ambient temperature |
-10℃ ~ +40℃ |
| Relative humidity |
5%~ 95%,no condensation |
| Altitude |
≤ 1500m,1500~3000m (derating 1% per 100m) according to GB / T3859.2 |
| Environmental conditions |
no harmful gas and steam, no conductive or explosive dust, no severe mechanical vibration |
| Outdoor installation |
At least 15cm space should be reserved for the upper and lower air outlets of the module, and at least 60cmspace should be reserved for the front and rear of the cabinet for easy maintenance. |
| Relative humidity |
Relative humidity:When the temperature is + 25 ℃ , the relative humidity can reach 100% in a short time |
| System parameters |
|
| Rated input line voltage |
380V (-20% ~ +20%) |
| Rated frequency |
50Hz ( 45Hz ~ 55Hz) |
| Power grid structure |
3P3W/3P4W (400V) |
| Current transformer |
100/5 ~ 5,000/5 |
| Circuit topology |
three-level |
| Overall eifficiency |
≥ 97% |
| Standard |
CQC1311-2017、DL/T1216-2013、JB/T11067-2011 |
| Performance |
| Three-phase balance compensation capability |
Imbalance < 3% |
| Target power factor |
1, Response time < 10ms |
| Reactive power compensation rate |
> 99% |
| Protective function |
Over-voltage protection, under-voltage protection, short-circuit protection, over-current protection, overtemperature protection, drive fault protection,lightning protection |
| Power distribution function |
With C-level lightning protection function |
| Communication monitoring capability |
| Display content |
Real-time operating information such as voltage, current, power factor, and operating temperature |
| Communication interface |
Standard RS485 interface, optional wifi or GPRS, (only one communication mode can be selected for the same device) |
| Communication protocol |
Modbus protocol |
| Mechanical properties |
| Mounting type |
F or H pole, installation inclination < 5 ℃ |
| IP grade |
IP grade |
| Dimension and structure |
capacity(kavr) |
front door opening |
side door opening |
weight(kg) |
holedimension |
| Dimension(W×H×D) |
mountingdimension(W×D) |
Dimension(W×H×D) |
mountingdimension (W×D) |
 |
35 |
760×1150×470 |
624×250 |
780×1110×620 |
644×350 |
50 |
4-Φ13 |
| 70 |
760×1150×470 |
624×250 |
780×1110×620 |
644×350 |
75 |
4-Φ13 |
| 100 |
760×1150×470 |
624×250 |
780×1110×620 |
644×350 |
95 |
4-Φ13 |
Product detail pictures:
Related Product Guide:
Our advantages are lessen charges,dynamic income team,specialized QC,sturdy factories,premium quality services for Power Quality Cabinet – HYSPC three-phase load imbalance automatic adjustment device – LASTONE , The product will supply to all over the world, such as: Italy, Tanzania, Lahore, Besides strong technical strength, we also introduce advanced equipment for inspection and conduct strict management. All the staff of our company welcome friends both at home and abroad to come for visits and business on the basis of equality and mutual benefit. If you are interested in any of our items, please feel free to contact us for quotation and product details.