We know that we only thrive if we will guarantee our combined cost competiveness and high-quality advantageous at the same time for Air Conditioner Capacitor, Power Capacitor, Ac Filter Capacitor, As a result of our hard perform, we have always been around the forefront of clean technology merchandise innovation. We've been a eco-friendly partner you can rely on. Get hold of us today for additional data!
China Wholesale Reactive Power Controller Quotes - JKGHYBA580 intelligent combination low voltage reactive power measuring & controller – LASTONE Detail:
Overview
JKGHYBA580 intelligent combination low voltage reactive power measuring&controller device is new type of low voltage reactive power compensation controller that integrates measurement, control and display.
It mainly integrates normal voltmeters, ammeters, power factor meters, reactive power meters, and active power meters in one controller, It can also display three phase compensation current and capacitor switching status display. This product adopts RS485 communication method, which can connect up to 20 pieces of HY series combined low voltage power capacitors.
Model and Meaning
HKG |
HY |
BA |
- |
580-l |
- |
□□ |
| |
| |
| |
|
| |
|
| |
1 |
2 |
3 |
|
4 |
|
5 |
No. |
Name |
|
1 |
Controller type |
|
2 |
Enterprise code |
|
3 |
Automatic control |
|
4 |
Specification |
580:normal type 580-l:special made (equipped with anti-harmonic) |
5 |
Procedure category |
|
*Note:JKGHYBA580-l is equipped with HYBAGK
Technical Parameters
Normal working and installation conditions
Ambient temperature |
-25°C ~ +55°C |
Relative humidity |
≤ 50% at 40°C ; ≤ 90% at 20°C |
Altitude |
≤ 2000m |
Environmental conditions |
no harmful gas and steam, no conductive or explosive dust, no severe mechanical vibration |
Power condition |
|
Rated voltage 220V±20%; THDvm5%;
Rated frequency 50Hz±5Hz
Performance
Measurement accuracy |
voltage: ≤ ±0.5%(0.8-1.2Un)/ current: ≤ ±0.5%(0.2-1.2ln)/ active power reactive ≤ ±2%, reactive power: ≤ ±2%, power factor: ≤ ±1% |
Control quantity |
20 Pieces |
Compensation method |
three phase compensation or mixed compensation |
Control method |
RS485 |
Protective function |
Over-voltage protection, under-voltage protection, under-current protection, over-harmonic protection |
Standard |
JB/T 9663-2013 |
Dimension and structure |
Dimension(WxHxD) Mounting dimension(WxH) |
 |
170x170x120 |
160×160 |
Product detail pictures:
Related Product Guide:
Our commission should be to provide our customers and consumers with ideal top quality and aggressive portable digital products for China Wholesale Reactive Power Controller Quotes - JKGHYBA580 intelligent combination low voltage reactive power measuring & controller – LASTONE , The product will supply to all over the world, such as: Los Angeles, Provence, Puerto Rico, Our products are widely recognized and trusted by users and can meet continuously changing economic and social needs. We welcome new and old customers from all walks of life to contact us for future business relationships and mutual success!