"Based on domestic market and expand abroad business" is our enhancement strategy for Active Power Filter Reactor, Best Capacitors For Power Supply Filtering, Capacitor Start Capacitor Run Motor, Special emphasis around the packaging of merchandise to avoid any damage during transportation,Detailed interest into the useful feedback and strategies of our esteemed shoppers.
China Wholesale Reactive Power Compensation Pricelist - Three phase series filter reactor – LASTONE Detail:
Overview
CKSG series three phase series filter reactors are often affected by harmonic current, switching inrush current and operating overvoltage when compensating capacitive reactive power, which will cause capacitor damage and power factor reduction. Install three phase filter reactors to suppress and absorb harmonics, protect capacitors, avoid the effects of harmonic voltage current and impulse voltage current, improve power quality, increase system power factor, and extend capacitor life
Standard:
● GB/T 1094.6-2011
● GB/T 19212.1-2016
Features
● Designed with secondary thermal sensitive temperature protection switch
● Full vacuum dipping process, low noise during operation
● Winding frame is reinforced environmental protection flame retardant plastic
Model and Meaning
CKSG |
- 
|
-
|
-7%
|
P |
K |
│ |
│ |
│ |
│ |
│ |
│ |
1 |
2 |
3 |
4 |
5 |
6 |
No. |
Name |
Meaning |
1 |
Series code |
Dry air-cooled three phase series filter reactor CKDG: single phase |
2 |
Matching Capacitor rated voltage (kV) |
|
3 |
Rated capacity of matched capacitor (kvar) |
|
4 |
Rated reactance rate XL / Xc (%) |
△ :three phase compensation; Y:split phase compensation |
5 |
P: terminal block |
RS485 |
6 |
K: with temperature protection switch |
No mark: without temperature protection switch |
Technical Parameters
Normal working and installation conditions
Ambient temperature |
-25°C~+50°C |
Relative humidity |
Relative humidity ≤ 50% at 40°C ; ≤ 90% at 20°C |
Altitude |
≤ 1000m |
Performance |
|
Rated voltage of capacitor |
0.4 kV、0.45 kV、0.48 kV、0.525 kV、0.66kV、0.69 kV; |
Reactance ratio |
Reactance rate 4.5%, 5%, 6%, 7% is used to limit switching inrush current and suppress 5th and above harmonics
|
Reactance ratio |
Reactance rate 12%, 14%, used to limit closing switching current and suppress 3rd and above harmonics
|
Withstand voltage level 3.5kV / min |
5kV/min |
Insulation class |
B, F, H; Noise ≤ 45dBz continuous operation under overload capacity ≤ 1.35ln |
Dimension and structure |
Product category |
Specification |
Dimension WxDx H(mm) |
Mounting dimensiWxD(mm) |
 |
CKSG 7% copper wire |
5~10 kvar |
210x145x170 |
110×85
|
15-25 kvar |
210x155x175 |
110×85
|
30-50 kvar |
240x160x215 |
135×110
|
CKSG 7% Aluminum wire |
5~8 kvar |
210x150x170 |
110×85
|
10-15 kvar
|
210x150x170 |
110×85
|
20-25 kvar
|
240x155x195 |
135×110
|
30-35 kvar
|
240x155x215 |
135×110
|
40-50 kvar
|
262x180x215 |
150×110
|
CKSG 14% copper wire |
25-30 kvar
|
240x160x200 |
135×110
|
CKSG 14% Aluminum wire |
25-30 kvar
|
270x190x215 |
150×120
|
CKSG 14% copper wire. Aluminum wire |
40-50 kvar
|
290x190x240 |
180×120
|
Product detail pictures:
Related Product Guide:
Dedicated to strict top quality command and considerate purchaser support, our experienced staff customers are always available to discuss your necessities and be certain full client gratification for China Wholesale Reactive Power Compensation Pricelist - Three phase series filter reactor – LASTONE , The product will supply to all over the world, such as: Porto, Angola, Swiss, We've got constructed strong and long co-operation relationship with an enormous quantity of companies within this business overseas. Immediate and specialist after-sale service supplied by our consultant group has happy our buyers. In depth Info and parameters from the merchandise will probably be sent to you for any thorough acknowledge. Free samples may be delivered and company check out to our corporation. n Portugal for negotiation is constantly welcome. Hope to get inquiries type you and construct a long-term co-operation partnership.