So that you can finest fulfill client's demands, all of our operations are strictly performed in line with our motto "High Excellent, Competitive Price, Fast Service" for Mars Motor Run Capacitor, Electrical Harmonic Filter, Detuned Filter, We wish to just take this opportunity to ascertain long-term enterprise relationships with clients from all over the earth.
China Wholesale Power Factor Improving Reactor Quotes - Three phase series filter reactor – LASTONE Detail:
Overview
CKSG series three phase series filter reactors are often affected by harmonic current, switching inrush current and operating overvoltage when compensating capacitive reactive power, which will cause capacitor damage and power factor reduction. Install three phase filter reactors to suppress and absorb harmonics, protect capacitors, avoid the effects of harmonic voltage current and impulse voltage current, improve power quality, increase system power factor, and extend capacitor life
Standard:
● GB/T 1094.6-2011
● GB/T 19212.1-2016
Features
● Designed with secondary thermal sensitive temperature protection switch
● Full vacuum dipping process, low noise during operation
● Winding frame is reinforced environmental protection flame retardant plastic
Model and Meaning
CKSG |
- 
|
-
|
-7%
|
P |
K |
│ |
│ |
│ |
│ |
│ |
│ |
1 |
2 |
3 |
4 |
5 |
6 |
No. |
Name |
Meaning |
1 |
Series code |
Dry air-cooled three phase series filter reactor CKDG: single phase |
2 |
Matching Capacitor rated voltage (kV) |
|
3 |
Rated capacity of matched capacitor (kvar) |
|
4 |
Rated reactance rate XL / Xc (%) |
△ :three phase compensation; Y:split phase compensation |
5 |
P: terminal block |
RS485 |
6 |
K: with temperature protection switch |
No mark: without temperature protection switch |
Technical Parameters
Normal working and installation conditions
Ambient temperature |
-25°C~+50°C |
Relative humidity |
Relative humidity ≤ 50% at 40°C ; ≤ 90% at 20°C |
Altitude |
≤ 1000m |
Performance |
|
Rated voltage of capacitor |
0.4 kV、0.45 kV、0.48 kV、0.525 kV、0.66kV、0.69 kV; |
Reactance ratio |
Reactance rate 4.5%, 5%, 6%, 7% is used to limit switching inrush current and suppress 5th and above harmonics
|
Reactance ratio |
Reactance rate 12%, 14%, used to limit closing switching current and suppress 3rd and above harmonics
|
Withstand voltage level 3.5kV / min |
5kV/min |
Insulation class |
B, F, H; Noise ≤ 45dBz continuous operation under overload capacity ≤ 1.35ln |
Dimension and structure |
Product category |
Specification |
Dimension WxDx H(mm) |
Mounting dimensiWxD(mm) |
 |
CKSG 7% copper wire |
5~10 kvar |
210x145x170 |
110×85
|
15-25 kvar |
210x155x175 |
110×85
|
30-50 kvar |
240x160x215 |
135×110
|
CKSG 7% Aluminum wire |
5~8 kvar |
210x150x170 |
110×85
|
10-15 kvar
|
210x150x170 |
110×85
|
20-25 kvar
|
240x155x195 |
135×110
|
30-35 kvar
|
240x155x215 |
135×110
|
40-50 kvar
|
262x180x215 |
150×110
|
CKSG 14% copper wire |
25-30 kvar
|
240x160x200 |
135×110
|
CKSG 14% Aluminum wire |
25-30 kvar
|
270x190x215 |
150×120
|
CKSG 14% copper wire. Aluminum wire |
40-50 kvar
|
290x190x240 |
180×120
|
Product detail pictures:
Related Product Guide:
We've got a specialist, effectiveness staff to supply high quality service for our shopper. We always follow the tenet of customer-oriented, details-focused for China Wholesale Power Factor Improving Reactor Quotes - Three phase series filter reactor – LASTONE , The product will supply to all over the world, such as: New Orleans, Toronto, Orlando, Now, we are trying to enter new markets where we do not have a presence and developing the markets we have the already penetrated. On account of superior quality and competitive price , we will be the market leader, please don’t hesitate to contact us by phone or email, if you are interested in any of our products.