we are able to supply top quality items, aggressive price and greatest buyer assistance. Our destination is "You come here with difficulty and we offer you a smile to take away" for Cbb60 Run Capacitor, Reactive Power Compensation, Cd60 Start Capacitor, We believe this sets us apart from the competition and makes customers choose and trust us. We all wish to create win-win deals with our customers, so give us a call today and make a new friend!
China Wholesale Power Factor Improving Reactor Pricelist - Three phase series filter reactor – LASTONE Detail:
Overview
CKSG series three phase series filter reactors are often affected by harmonic current, switching inrush current and operating overvoltage when compensating capacitive reactive power, which will cause capacitor damage and power factor reduction. Install three phase filter reactors to suppress and absorb harmonics, protect capacitors, avoid the effects of harmonic voltage current and impulse voltage current, improve power quality, increase system power factor, and extend capacitor life
Standard:
● GB/T 1094.6-2011
● GB/T 19212.1-2016
Features
● Designed with secondary thermal sensitive temperature protection switch
● Full vacuum dipping process, low noise during operation
● Winding frame is reinforced environmental protection flame retardant plastic
Model and Meaning
| CKSG |
- 
|
-
|
-7%
|
P |
K |
| │ |
│ |
│ |
│ |
│ |
│ |
| 1 |
2 |
3 |
4 |
5 |
6 |
| No. |
Name |
Meaning |
| 1 |
Series code |
Dry air-cooled three phase series filter reactor CKDG: single phase |
| 2 |
Matching Capacitor rated voltage (kV) |
|
| 3 |
Rated capacity of matched capacitor (kvar) |
|
| 4 |
Rated reactance rate XL / Xc (%) |
△ :three phase compensation; Y:split phase compensation |
| 5 |
P: terminal block |
RS485 |
| 6 |
K: with temperature protection switch |
No mark: without temperature protection switch |
Technical Parameters
Normal working and installation conditions
| Ambient temperature |
-25°C~+50°C |
| Relative humidity |
Relative humidity ≤ 50% at 40°C ; ≤ 90% at 20°C |
| Altitude |
≤ 1000m |
| Performance |
|
| Rated voltage of capacitor |
0.4 kV、0.45 kV、0.48 kV、0.525 kV、0.66kV、0.69 kV; |
| Reactance ratio |
Reactance rate 4.5%, 5%, 6%, 7% is used to limit switching inrush current and suppress 5th and above harmonics
|
| Reactance ratio |
Reactance rate 12%, 14%, used to limit closing switching current and suppress 3rd and above harmonics
|
| Withstand voltage level 3.5kV / min |
5kV/min |
| Insulation class |
B, F, H; Noise ≤ 45dBz continuous operation under overload capacity ≤ 1.35ln |
| Dimension and structure |
Product category |
Specification |
Dimension WxDx H(mm) |
Mounting dimensiWxD(mm) |
 |
CKSG 7% copper wire |
5~10 kvar |
210x145x170 |
110×85
|
| 15-25 kvar |
210x155x175 |
110×85
|
| 30-50 kvar |
240x160x215 |
135×110
|
| CKSG 7% Aluminum wire |
5~8 kvar |
210x150x170 |
110×85
|
|
10-15 kvar
|
210x150x170 |
110×85
|
|
20-25 kvar
|
240x155x195 |
135×110
|
|
30-35 kvar
|
240x155x215 |
135×110
|
|
40-50 kvar
|
262x180x215 |
150×110
|
| CKSG 14% copper wire |
25-30 kvar
|
240x160x200 |
135×110
|
| CKSG 14% Aluminum wire |
25-30 kvar
|
270x190x215 |
150×120
|
| CKSG 14% copper wire. Aluminum wire |
40-50 kvar
|
290x190x240 |
180×120
|
Product detail pictures:
Related Product Guide:
Bear "Customer first, Quality first" in mind, we work closely with our customers and provide them with efficient and professional services for China Wholesale Power Factor Improving Reactor Pricelist - Three phase series filter reactor – LASTONE , The product will supply to all over the world, such as: Kenya, Honduras, Jordan, If any item be of interest to you, you should let us know. We will try our best to satisfy your requirements with high quality goods, the best prices and prompt delivery. You should feel free to contact us at any time. We will reply you when we receive your inquiries. Make sure you note that samples are available before we start our business.