we can offer high quality products, competitive price and best customer service. Our destination is "You come here with difficulty and we give you a smile to take away" for Capacitor 50 60hz 250vac, Universal Start Capacitor, Cbb60 Sh Capacitor, For more info, be sure to call us as shortly as possible!
China Wholesale Intelligent Controller Factories - JKGHYBA580 intelligent combination low voltage reactive power measuring & controller – LASTONE Detail:
Overview
JKGHYBA580 intelligent combination low voltage reactive power measuring&controller device is new type of low voltage reactive power compensation controller that integrates measurement, control and display.
It mainly integrates normal voltmeters, ammeters, power factor meters, reactive power meters, and active power meters in one controller, It can also display three phase compensation current and capacitor switching status display. This product adopts RS485 communication method, which can connect up to 20 pieces of HY series combined low voltage power capacitors.
Model and Meaning
| HKG |
HY |
BA |
- |
580-l |
- |
□□ |
| | |
| |
| |
|
| |
|
| |
| 1 |
2 |
3 |
|
4 |
|
5 |
| No. |
Name |
|
| 1 |
Controller type |
|
| 2 |
Enterprise code |
|
| 3 |
Automatic control |
|
| 4 |
Specification |
580:normal type 580-l:special made (equipped with anti-harmonic) |
| 5 |
Procedure category |
|
*Note:JKGHYBA580-l is equipped with HYBAGK
Technical Parameters
Normal working and installation conditions
| Ambient temperature |
-25°C ~ +55°C |
| Relative humidity |
≤ 50% at 40°C ; ≤ 90% at 20°C |
| Altitude |
≤ 2000m |
| Environmental conditions |
no harmful gas and steam, no conductive or explosive dust, no severe mechanical vibration |
| Power condition |
|
Rated voltage 220V±20%; THDvm5%;
Rated frequency 50Hz±5Hz
Performance
| Measurement accuracy |
voltage: ≤ ±0.5%(0.8-1.2Un)/ current: ≤ ±0.5%(0.2-1.2ln)/ active power reactive ≤ ±2%, reactive power: ≤ ±2%, power factor: ≤ ±1% |
| Control quantity |
20 Pieces |
| Compensation method |
three phase compensation or mixed compensation |
| Control method |
RS485 |
| Protective function |
Over-voltage protection, under-voltage protection, under-current protection, over-harmonic protection |
| Standard |
JB/T 9663-2013 |
| Dimension and structure |
Dimension(WxHxD) Mounting dimension(WxH) |
 |
170x170x120 |
160×160 |
Product detail pictures:
Related Product Guide:
We rely upon strategic thinking, constant modernisation in all segments, technological advances and of course upon our employees that directly participate inside our success for China Wholesale Intelligent Controller Factories - JKGHYBA580 intelligent combination low voltage reactive power measuring & controller – LASTONE , The product will supply to all over the world, such as: Belarus, Peru, Canberra, Our products are sold to the Middle East, Southeast Asia, Africa, Europe, America and other regions, and are favorably appraised by clients. To benefit from our strong OEM/ODM capabilities and considerate services, please contact us today. We will sincerely create and share success with all clients.