"Sincerity, Innovation, Rigorousness, and Efficiency" would be the persistent conception of our corporation to the long-term to establish collectively with customers for mutual reciprocity and mutual benefit for Mars Run Capacitor, Motor Capacitor, Ac Motor Starter Capacitor, You should send us your specifications and requirements, or feel totally free to speak to us with any questions or inquiries that you may have.
China Wholesale Electric Reactor Suppliers - Three phase series filter reactor – LASTONE Detail:
Overview
CKSG series three phase series filter reactors are often affected by harmonic current, switching inrush current and operating overvoltage when compensating capacitive reactive power, which will cause capacitor damage and power factor reduction. Install three phase filter reactors to suppress and absorb harmonics, protect capacitors, avoid the effects of harmonic voltage current and impulse voltage current, improve power quality, increase system power factor, and extend capacitor life
Standard:
● GB/T 1094.6-2011
● GB/T 19212.1-2016
Features
● Designed with secondary thermal sensitive temperature protection switch
● Full vacuum dipping process, low noise during operation
● Winding frame is reinforced environmental protection flame retardant plastic
Model and Meaning
CKSG |
- 
|
-
|
-7%
|
P |
K |
│ |
│ |
│ |
│ |
│ |
│ |
1 |
2 |
3 |
4 |
5 |
6 |
No. |
Name |
Meaning |
1 |
Series code |
Dry air-cooled three phase series filter reactor CKDG: single phase |
2 |
Matching Capacitor rated voltage (kV) |
|
3 |
Rated capacity of matched capacitor (kvar) |
|
4 |
Rated reactance rate XL / Xc (%) |
△ :three phase compensation; Y:split phase compensation |
5 |
P: terminal block |
RS485 |
6 |
K: with temperature protection switch |
No mark: without temperature protection switch |
Technical Parameters
Normal working and installation conditions
Ambient temperature |
-25°C~+50°C |
Relative humidity |
Relative humidity ≤ 50% at 40°C ; ≤ 90% at 20°C |
Altitude |
≤ 1000m |
Performance |
|
Rated voltage of capacitor |
0.4 kV、0.45 kV、0.48 kV、0.525 kV、0.66kV、0.69 kV; |
Reactance ratio |
Reactance rate 4.5%, 5%, 6%, 7% is used to limit switching inrush current and suppress 5th and above harmonics
|
Reactance ratio |
Reactance rate 12%, 14%, used to limit closing switching current and suppress 3rd and above harmonics
|
Withstand voltage level 3.5kV / min |
5kV/min |
Insulation class |
B, F, H; Noise ≤ 45dBz continuous operation under overload capacity ≤ 1.35ln |
Dimension and structure |
Product category |
Specification |
Dimension WxDx H(mm) |
Mounting dimensiWxD(mm) |
 |
CKSG 7% copper wire |
5~10 kvar |
210x145x170 |
110×85
|
15-25 kvar |
210x155x175 |
110×85
|
30-50 kvar |
240x160x215 |
135×110
|
CKSG 7% Aluminum wire |
5~8 kvar |
210x150x170 |
110×85
|
10-15 kvar
|
210x150x170 |
110×85
|
20-25 kvar
|
240x155x195 |
135×110
|
30-35 kvar
|
240x155x215 |
135×110
|
40-50 kvar
|
262x180x215 |
150×110
|
CKSG 14% copper wire |
25-30 kvar
|
240x160x200 |
135×110
|
CKSG 14% Aluminum wire |
25-30 kvar
|
270x190x215 |
150×120
|
CKSG 14% copper wire. Aluminum wire |
40-50 kvar
|
290x190x240 |
180×120
|
Product detail pictures:
Related Product Guide:
Persisting in "High top quality, Prompt Delivery, Aggressive Price", now we have established long-term cooperation with customers from the two overseas and domestically and get new and aged clients' large comments for China Wholesale Electric Reactor Suppliers - Three phase series filter reactor – LASTONE , The product will supply to all over the world, such as: Leicester, Dubai, Eindhoven, We pay high attention to customer service, and cherish every customer. We have maintained a strong reputation in the industry for many years. We are honest and work on building a long-term relationship with our customers.